Honeywell DPR 100C via 3150-MCM

Problem Solution Overview

We performed testing between the subject device and our 3150-MCM product.

Solution Brief

Our testing generated the following results:

  • We were able to successfully communicate with the device. (see below for configuration parameters used during the testing)
  • The product supports Modbus function codes 4, 6, 16 for data movement. In addition, the DPR 100C supports several function codes ( 8, 20, 21) which the MCM does not support. These additional codes are not required for a successful connection.

Configuration:

The product testing was performed with the following settings .
- Baud: 9600
- Parity: None
- Stop: 1
- Mode: RTU Master Mode
- Physical Connection : RS-485 (2 wire connection)

The Module Configuration used in our testing was as follows:

Address

0

1

2

3

4

5

6

7

8

9

N7:0

0

0

5

0

0

0

0

0

0

0

N7:10

0

0

5

0

0

0

0

0

0

0

N7:20

4

1

2

130

150

0

0

0

4

0

This configuration, in combination with the example ladder logic referenced below, generates the following memory map:

N10:0 to N10:129 - Slave Data
N10:200 to N10:249 - Write Data
N10:130 to N10:149 - Slave Error Table (Contains revision level information also)
N10:150 to N10:199 - Master Error Table (Contains status of commands for diagnostics)

Command List:

The following command list shows some of the commands which were used to test the communications:

Address

0
Port
Number

1
Slave
Number

2
Function
Code

3
Source
Address

4
Count

5
Dest.
Address

6
Read
Type

N7:50

1

1

4

6144

6

0

0

N7:60

1

1

4

256

1

20

0

N7:70

5

1

16

200

4

768

0

N7:80

0

0

0

0

0

0

0

N7:90

0

0

0

0

0

0

0

test command list performs the following functions.

Cable Connection:

The physical connection which was used during testing was as follows:

MCM Module

 

Device

TXDRXD +

--------------------------------

RX / TX B

TXDRXD -

--------------------------------

RX / TX A

RTS

----------|

 

CTS

----------|

Jumper between RTS/CTS
on module must be installed

GND

   

For ease of installation, termination on the ProSoft module was accomplished using our screw termination adaptor for the DB-9 plug. A similar screw termination plug is also available for the DB-25 required for the 3100-MCM.

The part number for these is:
1451-9F : DB-9 to RS-422/RS-485 Screw Terminals (for 3150-MCM)
1452-25M : DB-25 to RS-422/RS-485 Screw Terminals (for 3100-MCM)