Valvcon IVO (Intelligent Valve Operator) via 3100-MCM

Problem Solution Overview

We performed testing between the subject device and our 3100-MCM product.

Solution Brief

Our testing generated the following results:

  • We were able to successfully communicate with the device. (see below for configuration parameters used during the testing)
  • The product supported Modbus functions 3,4 & 6
  • The average message response time was 5 ms.

Configuration:

The product testing was performed with the following settings used:
- Baud: 9600
- Parity: None
- Stop: 1
- Mode: RTU Master Mode
- Physical Connection : RS-485

The Module Configuration used in our testing was as follows:

Address

0

1

2

3

4

5

6

7

8

9

N7:0

0

0

5

0

0

0

0

0

0

0

N7:10

1

1

5

0

0

0

0

0

0

0

N7:20

4

1

2

130

150

0

0

0

4

0

This configuration, in combination with the example ladder logic referenced below, generates the following memory map:

N10:0 to N10:129 - Slave Data
N10:130 to N10:149 - Slave Error Table (Contains revision level information also)
N10:150 to N10:199 - Master Error Table (Contains status of commands for diagnostics)

Command List:

The following command list shows some of the commands which were used to test the communications:

Address

0
Port
Number

1
Slave
Number

2
Function
Code

3
Source
Address

4
Count

5
Dest
Address

6
Read
Time

7
Polling
Time
Preset

N7:50

1

1

3

8

1

0

0

0

N7:60

1

1

4

7

1

1

0

0

N7:70

1

1

6

200

0

1

0

0

N7:80

1

1

6

201

0

0

0

0

Our test command list perfoms the following functions.

Cable Connection:

The physical connection which was used during testing was as follows:

3100-MCM Module

 

Valvcon J5 connections

14 TxRxD+

----------------------

J5 - 6

25 TxRxD-

----------------------

J5 - 5

7 GND

----------------------

J5 - 4

4 RTS

----------|

 

5 CTS

----------|

 

Additional Comments and Observations:

  1. The cable connections listed are based on CPU Board 1519 J5 terminal block for RS-485 two wire communications.
  2. When referring to the Valvcon documentation remember to use subtract 1 from the listed address for use in our command list.