A-B 1336, 1336 Plus, 1305 Micro
Problem Solution Overview
The 1500-MBS (1336 Classic) and the 1550-MBS (1336 Plus & 1305 Micro) cards allow the Variable Frequency Drives to interface directly with a Modbus Master.
Solution Brief
These cards provide the following functionality for the AB Variable Frequency Drives: Multi-drop on an RS-422 or RS-485 link with other drives or other Modbus compatible devices interface via RS-232 with full radio / modem support be applied in existing or retrofit applications where other manufacturer's devices are in use.
Simple to Use
Preparing the 1500/1550-MBS card is accomplished by connecting the card to the drive's communication port, setting the card's configuration dip switches and cabling into the Modbus communication link.
Hands Off Operation
The 1500/1550-MBS card provides transparent control and monitoring capabilities, thus making the 1500/1550-MBS card & AB Drive combination a tightly integrated solution.
Example Applications
Applications involving the 1500/1550-MBS cards include many industrial sectors and the following:
- Food Processing Applications
- Mining Applications
- Pulp and Paper Applications
- HVAC Applications
Application Notes are available for these products.
Modbus Specifications
- The 1500/1550 products support the following capabilities:
- RTU mode (binary) with CRC-16 error checking
- Accepts broadcast commands from the Master
-
Function codes:
- 1: Read Output Status
- 2: Read Input Status
- 3: Read Multiple Output Registers
- 4: Read Multiple Input Registers
- 5: Force Single Coil (Write Single Bit)
- 6: Preset (Write) Single Data Register - 16: Preset (Write) Multiple Data Registers
-
Modbus Data Register addressing:
- Output Coils:1 to 1440
- Input Coils:10001 to 11440
- Output Registers:40001 to 40190 - Input Registers:30001 to 30190
- First 100 registers corresponding to the 1336 Drive Parameter Numbers (1500-MBS)
- Event Driven Control register writes correspond to the 1336 Drive Parameter Numbers (1500-MBS)
- Configuration via dip switches
-
Communication Parameters (1500-MBS):
- Address: 1 to 247
- Parity: None, Odd or Even
- Stop Bits: 1 or 2
- Baud Rate: 300 to 19.2 k Modbus Port - Baud Rate: 2400 or 9600 Drive Port
General Specifications
-
1500-MBS Specifications:
- 4"x5" form factor
- Two male 9-pin D shell connectors
- MBS port configurable for RS-232C or RS-422/485
- Status lights - Active and Fault for each port - 9 to 30 VDC external power
-
1550-MBS Specifications:
- ScanPort
- 120 VAC
- 9 pin female serial port
- supports RS-232, RS-422 and RS-485 - Tx, Rx, Serial and ScanPort status LED's
|