Valtek StarPac connectivity to 3100-MCM
Problem Solution Overview
We performed testing between the subject device and our 3100-MCM product.
Solution Brief
Our testing generated the following results:
- We were able to successfully communicate with the device. (see below for configuration parameters used during the testing)
- The product supported Modbus functions 3,4,6 & 16
The purpose of our testing is to assure a level of compatibility in the communications between the two products. Through this testing, we attempt to identify problem areas that may arise when implementing the interface in the field.
Configuration:
The product testing was perfomed with the following settings used for both devices.
- Baud: 19200
- Parity: Odd
- Stop: 1
- Mode: RTU Master Mode - Physical Connection : RS-485
The Module Configuration used in our testing was as follows:
|
Address
|
0
|
1
|
2
|
3
|
4
|
5
|
6
|
7
|
8
|
9
|
|
N7:0
|
16384
|
0
|
6
|
0
|
0
|
0
|
0
|
0
|
0
|
0
|
|
N7:10
|
16384
|
0
|
6
|
0
|
0
|
0
|
0
|
0
|
0
|
0
|
|
N7:20
|
4
|
1
|
2
|
130
|
150
|
0
|
0
|
0
|
4
|
0
|
This configuration, in combination with the example ladder logic referenced below, generates the following memory map:
N10:0 to N10:129 - Slave Data
N10:130 to N10:149 - Slave Error Table (Contains revision level information also) N10:150 to N10:199 - Master Error Table (Contains status of commands for diagnostics)
Command List:
The following command list shows some of the commands which were used to test the communications:
|
Address
|
0
Port Number
|
1
Slave Number
|
2
Function Code
|
3
Source Address
|
4 Count
|
5
Dest Address
|
6
Read Type
|
|
N7:50
|
1
|
1
|
3
|
260
|
2
|
50
|
0
|
|
N7:60
|
1
|
1
|
4
|
27
|
1
|
60
|
0
|
|
N7:70
|
1
|
1
|
6
|
200
|
1
|
37
|
0
|
|
N7:80
|
1
|
1
|
16
|
201
|
2
|
39
|
0
|
Our test command list performs the following functions.
- N7:50 Read register 70261 (floating point value)
- N7:60 Read alarm register
- N7:70 Set valve operating mode.
- N7:80 Set controller action & setpoint source selector
Cable Connection:
The physical connection which was used during testing was as follows:
|
MCM Module
|
|
Device
|
|
TXDRXD +
|
---------------------
|
User Terminal 11
|
|
TXDRXD -
|
---------------------
|
User Terminal 18
|
|
RTS
|
----------|
|
|
|
CTS
|
----------|
|
Jumper between RTS/CTS on module must be installed
|
|
GND
|
|
NA
|
For ease of installation, termination on the ProSoft module was accomplished using our screw termination adaptor for the DB-25 plug. A similar screw termination plug is also available for the DB-9 required for the 3150-MCM. The part number for these is:
1451-9F : DB-9 to RS-422/RS-485 Screw Terminals (for 3150-MCM) 1452-25M : DB-25 to RS-422/RS-485 Screw Terminals (for 3100-MCM)
|