Valtek StarPac connectivity to 3100-MCM

Problem Solution Overview

We performed testing between the subject device and our 3100-MCM product.

Solution Brief

Our testing generated the following results:

  • We were able to successfully communicate with the device. (see below for configuration parameters used during the testing)
  • The product supported Modbus functions 3,4,6 & 16

The purpose of our testing is to assure a level of compatibility in the communications between the two products. Through this testing, we attempt to identify problem areas that may arise when implementing the interface in the field.

Configuration:

The product testing was perfomed with the following settings used for both devices.

- Baud: 19200
- Parity: Odd
- Stop: 1
- Mode: RTU Master Mode
- Physical Connection : RS-485

The Module Configuration used in our testing was as follows:

Address

0

1

2

3

4

5

6

7

8

9

N7:0

16384

0

6

0

0

0

0

0

0

0

N7:10

16384

0

6

0

0

0

0

0

0

0

N7:20

4

1

2

130

150

0

0

0

4

0

This configuration, in combination with the example ladder logic referenced below, generates the following memory map:

N10:0 to N10:129 - Slave Data
N10:130 to N10:149 - Slave Error Table (Contains revision level information also)
N10:150 to N10:199 - Master Error Table (Contains status of commands for diagnostics)

Command List:

The following command list shows some of the commands which were used to test the communications:

Address

0
Port
Number

1
Slave
Number

2
Function
Code

3
Source
Address

4
Count

5
Dest
Address

6
Read
Type

N7:50

1

1

3

260

2

50

0

N7:60

1

1

4

27

1

60

0

N7:70

1

1

6

200

1

37

0

N7:80

1

1

16

201

2

39

0

Our test command list performs the following functions.

  1. N7:50 Read register 70261 (floating point value)
  2. N7:60 Read alarm register
  3. N7:70 Set valve operating mode.
  4. N7:80 Set controller action & setpoint source selector

Cable Connection:

The physical connection which was used during testing was as follows:

MCM Module

 

Device

TXDRXD +

---------------------

User Terminal 11

TXDRXD -

---------------------

User Terminal 18

RTS

----------|

 

CTS

----------|

Jumper between RTS/CTS
on module must be installed

GND

 

NA

For ease of installation, termination on the ProSoft module was accomplished using our screw termination adaptor for the DB-25 plug. A similar screw termination plug is also available for the DB-9 required for the 3150-MCM. The part number for these is:

1451-9F : DB-9 to RS-422/RS-485 Screw Terminals (for 3150-MCM)
1452-25M : DB-25 to RS-422/RS-485 Screw Terminals (for 3100-MCM)

Image Gallery



Contact Information


Flowserve
1350 Mountain Springs Pkwy
Springville, UT 84663
Phone: (801) 489-8611

Home : Products : Support : Distributors : Services : News/Events : Contact Us : ProSoft Tested