Applied Automation Totalflow 6400 connectivity to 3100-MCM

Problem Solution Overview

We performed testing between the subject device and our 3100-MCM product.

Solution Brief

Our testing generated the following results:

  • We were able to successfully communicate with the device. (see below for configuration parameters used during the testing)
  • The product supported Modbus functions 1,3,5,6 & 16
  • Message turn around for this unit averaged 30ms

The purpose of our testing is to assure a level of compatibility in the communications between the two products. Through this testing, we attempt to identify problem areas that may arise when implementing the interface in the field.

Configuration:

The product testing was perfomed with the following settings used.

- Baud: 19200
- Parity: None
- Stop: 1
- Mode: RTU Master Mode
- Physical Connection : RS-232

The Module Configuration used in our testing was as follows:

Address

0

1

2

3

4

5

6

7

8

9

N7:0

0

0

6

0

0

0

0

0

0

0

N7:10

1

1

6

0

0

0

0

0

0

0

N7:20

4

1

2

130

150

0

0

0

4

0

This configuration, in combination with the example ladder logic referenced below, generates the following memory map:

N10:0 to N10:129 - Slave Data
N10:130 to N10:149 - Slave Error Table (Contains revision level information also)
N10:150 to N10:199 - Master Error Table (Contains status of commands for diagnostics)

Command List:

The following command list shows some of the commands which were used to test the communications:

Address

0
Port
Number

1
Slave
Number

2
Function
Code

3
Source
Address

4
Count

5
Dest.
Address

6
Read
Type

N7:50

1

1

1

1001

1

0

0

N7:60

1

1

5

3200

1

1001

0

N7:70

1

1

16

201

10

110

0

N7:80

1

1

3

8001

10

10

0

Our test command list perfoms the following functions.

  1. N7:50 Read Binary register 1001.
  2. N7:60 Write Binary register 1001.
  3. N7:70 Setup user defined type.
  4. N7:80 Read back user defined type.

Cable Connection:

The physical connection which was used during testing was as follows:

3100-MCM
Module

 

Device

2 TXD

-------------------------

Terminal 4

3 RXD

-------------------------

Terminal 6

7 GND

-------------------------

Terminal 1

4 RTS

----------|

Terminal 8

5 CTS

----------|

Terminal 9

Note: RTS/CTS (Terminals 8 & 9) must be jumpered on the Totalflow as well.

Additional Comments and Observations:

  1. Register reads with a memory address greater then 5000 will return 2 words for each value requested. If you have a need to write to these registers please contact ProSoft Technology for further details.
  2. All registers in a custom group will be type cast to floating point before being returned.

Image Gallery