Fuji Electric Micro Controller PXR4
Problem Solution Overview
We performed testing between the subject device and our MVI56-MCM product.
Solution Brief
Our testing generated the following results:
- We were able to successfully communicate with the device. (see below for configuration parameters used during the testing)
- The product supported Modbus functions 1,2,3,4,5,6 & 16
The purpose of our testing is to assure a level of compatibility in the communications between the two products. Through this testing, we attempt to identify problem areas that may arise when implementing the interface in the field.
Configuration:
The product testing was performed with the following settings used:
- Baud: 9600
- Parity: None
- Stop: 1
- Mode: RTU Slave Mode - Physical Connection: RS-485
The MVI56-MCM Module Configuration used in our testing was as follows:
Command List
The following command list shows some of the commands, which were used to test the communications:
We found the Micro Controllers Manual to accurate clearly defined in regards to the modbus mapping and functions.
Cable Connection: (RS485)
The physical connection that was used during testing was as follows:
|
MVI56-MCM Module
|
|
Micro
|
|
1 RXTXD+
|
--------------------------
|
Term 7
|
|
8 RXTXD-
|
--------------------------
|
Term 8
|
|