ProSoft Technology, Inc.
  Your Location: ProSoft Tested > Solutions > Level Interfaces > Milltronics BIC II Printable Page
 

Search


Milltronics BIC II connectivity to 3100-MCM

Problem Solution Overview

We performed testing between the subject device and our 3100-MCM product.

Solution Brief

Our testing generated the following results:

  • We were able to successfully communicate with the device. (see below for configuration parameters used during the testing)
  • The product supported Modbus functions 3 & 6

The purpose of our testing is to assure a level of compatibility in the communications between the two products. Through this testing, we attempt to identify problem areas that may arise when implementing the interface in the field.

Configuration:

The product testing was performed with the following settings used for both devices.
- Baud: 19200
- Parity: Even
- Stop: 1
- Mode: ASCII 7 bit Master Mode
- Physical Connection : RS-422

The Module Configuration used in our testing was as follows:

Address

0

1

2

3

4

5

6

7

8

9

N7:0

-32766

0

6

0

0

0

0

0

0

0

N7:10

-32766

0

6

0

0

0

0

0

0

0

N7:20

4

1

2

130

150

0

0

0

4

0

This configuration, in combination with the example ladder logic referenced below, generates the following memory map:
N10:0 to N10:129 - Slave Data
N10:130 to N10:149 - Slave Error Table (Contains revision level information also)
N10:150 to N10:199 - Master Error Table (Contains status of commands for diagnostics)
Command List:

The following command list shows some of the commands which were used to test the communications:

Address

0
Port
Number

1
Slave
Number

2
Function
Code

3
Source
Address

4
Count

5
Dest.
Address

6
Read
Type

N7:50

1

1

6

200

1

7001

0

N7:60

1

1

3

0

1

0

0

Our test command list perfoms the following functions.

  1. N7:50 Initialize instruments port for use.
  2. N7:60 Retrieve status registers.

Cable Connection:

The physical connection which was used during testing was as follows:

MCM Module

Device

TXD +

-------------------

Terminal 13

TXD -

-------------------

Terminal 14

RXD +

-------------------

Terminal 16

RXD -

-------------------

Terminal 17

GND

-------------------

Terminal 12

RTS

---------|

 

CTS

---------|

Jumper between RTS/CTS
on module must be installed

For ease of installation, termination on the ProSoft module was accomplished using our screw termination adaptor for the DB-25 plug. A similar screw termination plug is also available for the DB-9 required for the 3150-MCM.

The part number for these is:
1451-9F : DB-9 to RS-422/RS-485 Screw Terminals (for 3150-MCM)
1452-25M : DB-25 to RS-422/RS-485 Screw Terminals (for 3100-MCM)

Additional Comments and Observations:

Proper instrument port initialization is critical for successful communications with the BIC II interface.