Moore APACS ACM connectivity to 3100-MCM

Problem Solution Overview

We performed testing between the subject device and our 3100-MCM product.

Solution Brief

Our testing generated the following results:

  • We were able to successfully communicate with the device. (see below for configuration parameters used during the testing)
  • The product supported Modbus functions 1, 2, 3, 4, 5, 6, 15 & 16

The purpose of our testing is to assure a level of compatibility in the communications between the two products. Through this testing, we attempt to identify problem areas that may arise when implementing the interface in the field.

Configuration:

The product testing was performed with the following settings used:

- Baud: 19200
- Parity: Even
- Stop: 1
- Mode: RTU Master Mode
- Physical Connection : RS-232

The Module Configuration used in our testing was as follows:

Address

0

1

2

3

4

5

6

7

8

9

N7:0

-32768

0

6

0

0

0

0

0

0

0

N7:10

1

1

6

0

0

0

0

0

0

0

N7:20

4

1

2

130

150

0

0

0

0

4

This configuration, in combination with the example ladder logic referenced below, generates the following memory map:

N10:0 to N10:129 - Slave Data
N10:130 to N10:149 - Slave Error Table (Contains revision level information also)
N10:150 to N10:199 - Master Error Table (Contains status of commands for diagnostics)

Command List:

The following command list shows some of the commands which were used to test the communications:

Address

0
Port
Number

1
Slave
Number

2
Function
Code

3
Source
Address

4
Count

5
Dest.
Address

6
Read
Type

7
Polling
Time
Preset

N7:50

1

2

1

0

16

0

0

0

N7:60

1

2

3

0

10

10

0

0

N7:70

1

2

3

500

2

20

1

0

N7:80

1

2

6

200

1

1

0

0

N7:90

1

2

16

201

4

2

0

0

Our test command list performs the following functions.

Cable Connection:

The physical connection which was used during testing was as follows:

3100-MCM
Module

 

APACS
ACM

2 TXD

------------------------

Pin 3

3 RXD

------------------------

Pin 2

7 GND

-----------|

Pin 5

4 RTS

-----------|

 

5 CTS

   

Additional Comments and Observations:

  1. You must use type 1 when retrieving floating point numbers.