CAL Controls CAL 3300 Connectivity to 3150-MCM

Problem Solution Overview

We performed testing between the subject device and our 3150-MCM product.

Solution Brief

Our testing generated the following results:

  • We were able to successfully communicate with the device. (see below for configuration parameters used during the testing)
  • The product supports Modbus function codes 1, 3, 5, 6, 16 for data movement.

Configuration:

The product testing was performed with the following settings used for both devices.
- Baud: 9600
- Parity: None
- Stop: 1
- Mode: RTU Master Mode
- Physical Connection : RS-232 (3 wire connection)

The Module Configuration used in our testing was as follows:

Address

0

1

2

3

4

5

6

7

8

9

N7:0

0

0

5

0

0

0

0

0

0

0

N7:10

1

1

5

0

0

0

0

0

0

0

N7:20

4

1

2

130

150

0

0

0

4

0

This configuration, in combination with the example ladder logic referenced below, generates the following memory map: N10:0 to N10:129 - Slave Data
N10:130 to N10:149 - Slave Error Table (Contains revision level information also)
N10:150 to N10:199 - Master Error Table (Contains status of commands for diagnostics)

Command List:

The following command list shows some of the commands which were used to test the communications:

Address

0
Port
Number

1
Slave
Number

2
Function
Node

3
Source
Address

4
Count

5
Dest.
Address

6
Read
Type

N7:50

1

1

3

28

1

0

0

N7:60

1

1

3

127

1

1

0

N7:70

5

1

6

200

1

127

0

N7:80

0

0

0

0

0

0

0

N8:90

0

0

0

0

0

0

0

Our test command list performs the following functions.

  1. N7:50 This command reads the Temperature variable and places the value into N10:0.
  2. N7:60 This command reads the value of SP_1 (setpoint 1) and places the value into N10:1.
  3. N7:70 This command writes a value from N10:200 and sets SP_1 (setpoint 1) in the CAL 3300.

Cable Connection:

The physical connection which was used during testing was as follows:

MCM Module

 

Device

Pin 2 Rx

--------------------------------

Pin 9 Tx

Pin 3 Tx

--------------------------------

Pin 10 Rx

Pin 5 Gnd

--------------------------------

Pin 11 Gnd

Pin 7 RTS

----------|

 

Pin 8 CTS

----------|

Jumper between RTS/CTS
on module must be installed

For ease of installation, termination on the ProSoft module was accomplished using our screw termination adaptor for the DB-9 plug. A similar screw termination plug is also available for the DB-25 required for the 3100-MCM.

The part number for these is:

1451-9F : DB-9 to RS-422/RS-485 Screw Terminals (for 3150-MCM)
1452-25M : DB-25 to RS-422/RS-485 Screw Terminals (for 3100-MCM)

Image Gallery



Contact Information


CAL Controls Inc
1117 S.Milwaukee Avenue
Libertyville, IL 60048
Phone: (847) 680 7080
Fax: (847) 816 6852

Home : Products : Support : Distributors : Services : News/Events : Contact Us : ProSoft Tested