Barber-Colman 7EC/7SF Controllers Connectivity to 3100-MCM

Problem Solution Overview

We performed testing between the subject device and our 3100-MCM product.

Solution Brief

Our testing generated the following results:

  • We were able to successfully communicate with the device. (see below for configuration parameters used during the testing)
  • The product supported Modbus functions 1,2,3,4,5,6,15 & 16 0.

The purpose of our testing is to assure a level of compatibility in the communications between the two products. Through this testing, we attempt to identify problem areas that may arise when implementing the interface in the field.

Configuration:

The product testing was perfomed with the following settings used:

- Baud: 19200
- Parity: None
- Stop: 1
- Mode: RTU Master Mode
- Physical Connection : RS-485

The Module Configuration used in our testing was as follows:

Address

0

1

2

3

4

5

6

7

8

9

N7:0

0

0

6

0

0

0

0

0

0

0

N7:10

1

1

6

0

0

0

0

0

0

0

N7:20

4

1

2

130

150

0

0

0

4

0

This configuration, in combination with the example ladder logic referenced below, generates the following memory map:

N10:0 to N10:129 - Slave Data
N10:130 to N10:149 - Slave Error Table (Contains revision level information also)
N10:150 to N10:199 - Master Error Table (Contains status of commands for diagnostics)

Command List:

The following command list shows some of the commands which were used to test the communications:

Address

0
Port
Number

1
Slave
Number

2
Function
Mode

3
Source
Number

4
Count

5
Dest.
Address

6
Read
Type

N7:50

1

1

1

218

1

0

0

N7:60

1

1

2

1

1

1

0

N7:70

1

1

3

1

5

10

0

N7:80

1

1

5

3200

1

218

0

N7:90

1

1

6

201

1

1

0

Our test command list perfoms the following functions.

  1. N7:50 Read local / remote control bit register.
  2. N7:60 Read auto / manual bit register.
  3. N7:70 Read set point, PID out, proprotional band, integral time value and derivative time value.
  4. N7:80 Write to local / remote control bit register.
  5. N7:90 Write to set point register.

Cable Connection:

The physical connection which was used during testing was as follows:

3100-MCM Module

 

7EC

14 TXD

--------------------------------

Terminal 10

25 RXD

--------------------------------

Terminal 11

7 GND

--------------------------------

Terminal 9

3100-MCM Module

 

7SF

14 TXD

--------------------------------

Terminal 11

25 RXD

--------------------------------

Terminal 12

7 GND

--------------------------------

Terminal 13

Additional Comments and Observations:

  1. Maximum length for function 3 & 4 is 20 words. Lengths greater then 20 will result in the controller returning an error 9.
  2. The Modbus addresses used in the product documentation should be used directly.
  3. The unit must be removed from its case to be placed into configuration mode.